DSC LTE Universal Wireless Commercial Fire Alarm Communicator LE4010CF

Brand: DSC

$0.00

PRODUCT OVERVIEW:

The DSC LE4010CF-AT is a universal, wireless, commercial fire cellular AT&T LTE alarm communicator that is compatible with control panels that communicate using the Contact ID or SIA (300 baud) formats. The LE4010CF-AT connects the commercial fire alarm control panel to the cellular AT&T LTE network and reports alarm signals directly to the GeoArm monitoring station receiver (Sur-Gard® System I-IP/II/III/IV/5). The LE4010CF-AT uses the cellular network to ensure low-cost, high-speed and reliable alarm communications.
In instances where the control panel does not support Contact ID or SIA (300 baud), the LE4010CF has inputs preset to transmit fire alarm, fire supervisory or system trouble. Alarm signals are transmitted directly without the need of a clearinghouse to the IP linecard of the monitoring station receiver (Sur-Gard System I IP/II/III/IV/5).
The LE4010CF is compliant with the latest requirements for Communications Methods as per UL864 and NFPA72 2010, 2013, and 2016 editions. It can be used in Fire Monitoring applications as a single communications technology, in which case any failure of the communications path shall be annunciated at the supervising station within 5 minutes (NFPA72 2010) or 1 hour (NFPA72 2013/2016) of the failure, or it can be used as part of a multiple communications technologies (for example in conjunction with a DACT). When used as a back-up provision shall be made to monitor the integrity of each communication path and failure of any communications path shall be annunciated at the GeoArm supervising station and at the protected premises within not more than 24 hours of the failure.
The LE4010CF can be used as either a Sole Communicator or as a Backup Communicator. When being used as a Sole Communicator the LE4010CF will replace the phone line connection on the panel and as soon as it detects that an alarm needs to be transmitted it will send the alarm across the Cellular network immediately. When being used as a backup the communicator assesses the connection to the PSTN phone line, and only in the event of a phone line failure will it send all alarm traffic across the Cellular network to the GeoArm monitoring station.
The LE4010CF is UL listed under File S4019, Listing guide UOXX, as a sole or backup communicator for Commercial Fire monitoring installations. When used as a sole communicator under NFPA72 2010 guidelines the LE4010CF will send its heartbeat once every 97 seconds ensuring that three heartbeats will be received at the supervising station within the 300 second window. When used as a sole communicator under NFPA72 2013/2016 guidelines the LE4010CF will send its heartbeat once every 5 minutes to monitor connectivity with the supervising station within the 1 hour window. When used as a backup communicator the LE4010CF will monitor the other communication method (DACT) and send a daily test transmission to the supervising station. The LE4010CF has been approved by the California State Fire Marshal (CSFM) pursuant to Section 13144.1 of the California Health and Safety Code.

KEY FEATURES:

  • Uses LTE cellular network for high-speed, reliable and low-cost communications to an IP receiver
  • Automatically switches to 3G (HSPA/HSPA+) if LTE service is not available
  • Dual-band UMTS/HSPA; Penta-Band LTE; Quad-Band GSM/EDGE radio
  • Bi-color wireless signal strength indicator
  • Compatible with 4-digit or 10-digit Contact ID communication format as described in SIA DC-05 Standard and SIA DC-03 Standard for 300 baud.
  • Compatible with control panels that communicate using the Contact ID or SIA (300 baud) formats
  • Full event reporting
  • 4 on-board inputs with NC, NO or SEOL supervision
  • 4 on-board outputs (open collector)
  • Activation and initialization via webuser or mobile interface provided by C24 Communications
  • PTM (Panel Transmission Monitor) switches from PSTN to cellular on unsuccessful communication attempts (up to four phone numbers)
  • Simulates landline
  • 12V 1.2 Ah battery (optional, not included)
  • Case Tamper Output
  • Landline overvoltage protection
  • DLS support for status, firmware updates and remote debug enable
  • Remote Firmware Upgrade
  • Compatible with Sur-Gard System I-IP/II/III/IV/5 monitoring station receivers
  • View communicator status directly from your mobile phone to support on-site or remote troubleshooting
  • Includes UL listed power supply, transformer and 7 Ah rechargeable battery
  • UL 864 listed
  • CSFM listed
(4 products available)
Quantity

SKU: LE4010CF

Categories: Fire, Intrusion, Alarm Panels & Keypads

  • Dimensions: 11.5" H x 10" W x 3" D (290mm x 254mm x 75mm)
  • Input Voltage: 13.8 Vdc (Class 2, power limited)
  • Compatible External Power Adapters (2-prong): DSC ADP1310(W)-NAU (US)/ADP1310(W)-NA (Canada)
  • Input Voltage/Input Current (Nominal): 120 VAC
  • Current Draw (without battery): 200 mA (standby), 400 mA (transmitting)
  • Operating Environment: 32° to 120°F (0° to 49°C)
  • Relative Humidity: 93% Maximum (non-condensing)
  • Battery: Sealed, rechargeable type, rated 12V/1.2Ah
  • Battery Charging Voltage (maximum): 13.75VDC
  • Battery Charging Current: 360mA
  • Battery Standby Time: 24 hours (Note: battery must be replaced every 3-5 years)
  • Weight (with optional battery): 12.8 lbs (5.8 kg)
  • Wireless Cellular 2G: 850/1900MHz
  • Wireless Cellular 3G: 850/1900MHz
  • Wireless Cellular LTE: Bands B2, B4, B5, B12, B13
  • Antenna Gain: 2.0dBi
  • UL Fire Listing: File S4019